Built on a 17-acre site in Princeton, New Jersey, the Briger Hall, Commons, and School of Engineering and Applied Sciences (SEAS) buildings at Princeton University have created a new “neighborhood” devoted to environmental studies and engineering. The series of connected buildings, totaling 666,000 square feet, contains state-of-the-art facilities and collaborative spaces to promote and enable breakthrough research (Fig. 1). The site features new academic and research laboratories, classrooms, offices, community spaces, and a library.

The architecture was shaped by a desire for the buildings to blend seamlessly into the current campus environment while furthering the University’s sustainability goals, both of which informed the choice of a hybrid structural system. Offices and common spaces, including multi-story atria, use exposed mass timber. Laboratories, which have strict vibration criteria, are framed in structural steel. A major design feature of the Commons Building is “the diagrid,” which is a novel timber-steel composite system (Fig. 2) that spans in two directions up to 85 feet and supports heavy green roof loading. At the base of each building, reinforced and post-tensioned concrete are used to support heavy landscaping and transfer columns above.

Mass Timber Construction and Sustainability

Princeton University has several sustainable campus design initiatives, which include goals of evaluating building systems and materials for their carbon impact and visually expressing sustainable building features. These specific goals influenced the project team to maximize the use of mass timber construction because it is less carbon intensive than concrete or steel construction and is exposed to direct view, which embodies the important environmental research taking place in the building. The use of mass timber was avoided in the areas with heavy landscaping and labs with strict vibration criteria. Instead, mass timber was utilized in offices and common areas, such as in the atria and student hubs, where it was structurally viable. In these areas, a steel structure and a timber structure were developed to evaluate cost impacts, and a parametric Life Cycle Analysis was performed to understand relative carbon impacts, which ultimately justified the timber’s cost premium. Accordingly, the project received supplemental funding for the timber from the Sustainability Advocacy Committee, a special program at Princeton University that assists projects with implementing strategies towards meeting sustainability goals.

Glulam beams and columns support the offices, corridors, and multi-story atria. Given the desire for quiet work and study spaces, the team studied using cross-laminated timber (CLT) floor panels with acoustic treatment on floors and walls, versus acoustic dowel-laminated timber (ADLT) floor panels with integrated acoustic insulation in the soffit. Ultimately, the ADLT worked best for the project, and proved to be more economical.

A European supplier that could meet the demands of a large project with a tight schedule, and who the timber contractor was familiar with, provided the sourcing, production, and fabrication of glulam members. Glulam members are European spruce grades (GL24, GL28, and GL32), and range in size from 9.5 inches x 14.2 inches to 15 inches x 31.5 inches. Glulam beams have a maximum span of about 33 feet in the atria areas and are used to support a hanging multi-story steel stair below (Fig. 3). The ADLT was sourced in North America (northwest United States and western Canada). The ADLT panels typically span 17.5 feet in the offices, and up to 21 feet in the atria areas. All timber members in the office areas were designed for a two-hour fire rating provided by a charring layer in accordance with NDS Chapter 16. Elsewhere, the timber was designed for a one-hour fire rating.

The timber structure is laterally supported by the steel labs, which, along with the concrete slab on metal deck, spans as a diaphragm to concrete shear walls at the east and west ends of the laboratory areas. Rebar for the timber topping slabs, which also are designed as diaphragms and serve as the finished floor, are designed for the transfer of lateral forces from the timber-framed zones into the steel-framed zones.

High Performance Laboratories and Facilities

For the laboratories, the design team presented various floor framing options that would meet the desired Class A Velocity Vibration Criteria of 2,000 mips. Ultimately, the team designed an innovative steel floor system constructed with back-to-back channels filled with concrete. The framing spans over 30 feet—with only 22.5 inches of structural depth—allowing for maximum floor-to-ceiling heights in the labs and no horizontal penetrations through the beams, greatly simplifying the complex coordination commonly required in the design of lab buildings. Paired channel members were prefabricated in the shop, erected as a single piece on site, and connected to the edges of the column flanges. Beams are spaced on the lab modules and align with the lab tables, allowing the lab service pipes to pass vertically between the channels, as needed (Fig. 4).

Commons Building and Diagrid

The Commons Building is at the intersection of multiple pedestrian walkways and functions as a central gathering place for students that is organized on a diagonal grid system. Like other public areas of the project, timber was desired for the Commons Building. Length-to-width ratios of the multi-use spaces and lobby are about 1-to-1, and therefore a true two-way spanning structure was desired for efficiency. However, two-way spanning floor systems in timber are difficult to achieve.

A novel composite steel-timber structure was devised, dubbed simply as “the diagrid,” to achieve the two-way span. Paired glulam beams, reinforced with steel plates, connect to steel nodes constructed with pipe or solid rounds. The steel plates are located along the top and bottom of the glulam beams and are also used at the member ends to ensure an elegant steel-to-steel moment connection at the nodes, minimizing the number of fasteners needed (Figs. 5-6). The timber geometry was held constant, whereas the steel and fasteners were optimized for the varying structural demands, thereby maintaining visual continuity while achieving structural efficiency. At the lobby to the engineering library, the diagrid is 30 inches deep and spans approximately 45 feet overhead. At the roof, the diagrid is 60 inches deep and spans approximately 85 feet over the multi-purpose room to 5-5/8 inches-diameter solid steel columns at the perimeter, which visually blend into the verticals of the facade system (Fig. 7). Fire protection of the diagrid steel plates is provided by the charring layer of the mass timber, and the steel nodes and columns are fire-protected by intumescent paint.

The paired glulam beams directly support the ADLT floor planks, resist local bending moments between nodes, and resist vertical shear forces to deliver loads to the steel plates. The steel plates resist cumulative tensile and compressive chord forces and resist global bending moments and shear forces at the nodes. The glulam is also sized to laterally brace the steel plates. Together, the glulam and steel act compositely to achieve the spans and two-way behavior required.

Due to the highly expressive structure, careful coordination with the building services was needed to achieve the design intent. A 6-inch service zone was created at the top of the diagrid, directly below the floor plank, to allow for piping and conduit coordination (Fig. 2). Roof drains were limited to the core areas to eliminate the need for exposed piping in the timber areas. This created a unique long distance roof sloping profile that was achieved with a two-layer topping slab sandwiched between varying thicknesses of insulation to reduce the weight of the build-up. The HVAC design removed ducts from the timber zones, instead pushing air through the concrete floor and walls. Duct penetrations through the diagrid around the perimeter were carefully coordinated to be in structurally advantageous locations.

Integrating the Project into the Hillside

To integrate the project into the surrounding campus and landscape, the design takes advantage of the site topography to limit the height of the buildings, where there is a roughly 20-foot grade change from north to south. To excavate for the basements and the ground floor, which have a below grade depth of up to 50 feet, a 3/8-mile-long support-of-excavation (SOE) wall was needed. After studying the impacts from various SOE systems, a soil nail and rock anchor wall was chosen, and was carefully integrated into the design, ensuring that the University Eating Club properties located to the north remained unaffected (Fig. 8).

To avoid the need for the narrow buildings to resist large, unbalanced lateral soil pressures from the hillside, which would impact the spatial planning of each building, the SOE wall was designed and detailed to be permanent with a Double Corrosion Protection system. Soil nails, rock anchors, their bearing plates, and hardware are protected with an epoxy coating and are encased in grout. In addition, groundwater flows down the campus hillside into Lake Carnegie, with historical streams indicated on Princeton University maps dating as far back as 1746. Briger Hall and SEAS interrupt a large portion of the hillside, so keeping water out of the buildings was paramount. Water collects behind the SOE wall and drains beneath the building structures to the south. The SOE wall was offset from the new buildings to enable the installation of traditional waterproofing on the face of the foundation walls, which was a priority for the owner. Aero Aggregate backfill was used to fill the void between the walls and to minimize the lateral forces delivered to the building structure.

The below grade floor, ground floor, and second floor are built with reinforced concrete. The second floor supports heavy loads from the campus landscape and public plazas and acts as a column transfer platform between the labs or offices above to the open concourse below. Transfer beams and slabs, typically 36 inches deep, utilize post-tensioning in critical areas to minimize concrete volume, cracking, and long-term deflections that would adversely impact the floors supported above (Fig. 9).

Facade System Support

To blend in with the existing campus fabric, the project’s facade design incorporates brick and field stone. Reinforced concrete walls, which also support the floors, are used as backup support for thick hand-cut field stone at the base of the Briger Hall and SEAS, as well as at the northern face and base of the Commons building. The office areas, meanwhile, are clad in brick. To minimize the weight of the brick supported by the mass timber structure and adhere to the project schedule, a ¾-inch thin set brick facade was panelized with windows and insulation and was assembled offsite on a secondary structural frame (Fig. 10). Glazing in the atria areas enhances transparency, and the labs feature a unitized curtain wall system with metal panels and windows.

Intersections: Weaving the Hybrid Structure Together

Connection details at the intersections of dissimilar materials are an important consideration for a hybrid structure. For Briger Hall, Commons, and SEAS, three intersections were considered: steel to concrete, timber to concrete, and timber to steel (Fig. 11). Adjustability was built into the details considering construction tolerance between the three different materials and construction trades, thermal expansion and contraction, and the volume change of the timber due to fluctuations in relative humidity. Embed connections to concrete were designed to allow up to +/- 3 inches of connection tolerance. Timber to concrete or steel was often detailed for the timber to land on a wide ledge to accommodate the tolerance, and to transfer load through bearing. Slotted connections were used in the composite steel-timber diagrid structure in both the node connections and the plate reinforcement. Detailing these intersections was a collaborative effort between the design and contracting teams.

Final Thoughts

The Briger Hall, Commons, and SEAS complex demonstrates a shift in structural engineering practice: as traditional design criteria must be adapted to modern sustainability goals, hybrid structural systems are becoming more necessary. The selection of the materials was not only about using each material where it performs best, but also where the material best aligned with the goals of the University. The project's hybrid approach to the structural design provides a model other designers can look to for effective ways to achieve their own project sustainability goals. ■

About the Authors

Michael Hopper is an Associate Partner with LERA in New York, NY. He serves on PTI’s DC-20 Building Design Committee and teaches in the Civil and Environmental Engineering Department at Princeton University.

Rachel Marek is an Associate with LERA in New York, NY. She is an undergraduate alumna of Princeton University.

William Dawson is an Associate with LERA in New York, NY, and is an adjunct professor in the Department of Civil, Environmental and Ocean Engineering at Stevens Institute of Technology .